FL-20A Fault Locator
The FL-20A is an automatic cable fault locator. Once connected by the operator, the FL-20A makes all necessary adjustments and determines the location of a failure. This removes the need for specialized training by operators and let anyone easily use the equipment.
Downloads & Questions
We often provide our spec sheets and manuals in multiple languages. Contact us to let us know what you need, and we will get it to you!
Technical Specifications
Major Features:
-
Identify Shorts/High Voltage Shorts/Opens
-
Fully Automated
-
Compact and Lightweight
PARAMETER
VALUE
Test Voltage Range
500v-20kV
Test Frequency
DC
Voltage Display
6-inch backlit color TFT touch screen
Accuracy 2% of reading
Fault Indication
Touch Screen Display
Fault Definitions
Open - A condition where a single conductor has no continuity from one end to the other
Metallic Short - Two conductors without insulation or. a conductor and a shield that physically come into contact with one another.
High-Voltage Short - Two conductors or a conductor and a shield which have no insulation between them but do not contact one another.
Power Requirements
100-240 volta AC, 50/60 Hz 2 amps
Output Power
6mA Maximum
Equipment Accuracy
Better than 1% of total cable length (dependent on accuracy of actual cable footage and product uniformity).
Cable Loop Resistance
Metallic Short - 50 milliohms minimum
High-Voltage Short - 300 milliohms minimum